with up to 5mm². acc.to FM standards
more than 5mm²: Different cores with white numbers
Or per customer' s requirement

DeviceNET fieldbus system is used for connection of industrial equipment.
It is a low cost network connection and has an open network standard.
One pair of wires transmits data and one pair of wires supplies power
Suitable for fixed installation or occasional movement

Conductor: stranded tinned copper
Insulation: foamed PE, PVC
Color: white*blue, rad*black
Shield: Pair shielding with foil, tinned copper overall braiding
Out jacket: see the table below
Color: purple ( Approximate RAL 4005 )

Flame retardancy meets the requirements of IEC 60332-1
It has good ability to resist external electromagnetic interference

Temperature range:-40℃ ~+ 80℃
Test voltage:1000V/min (AC)
Characteristic impedance:120 士 12 Ω(1~10MHz)

-
Core identification code -
Test voltage1000V/min (AC)
-
Rated Voltage300v
-
Minimum bending radiusFlexing: 15D(Cable O.D.)
Fixed installation: 15D(Cable O.D.) -
Temperature RangeFlexing: - 40° C ~ + 80° C
-
Characteristic Impedance110 ±15 Ω ( 1MHz )
100 ± 6 Ω ( 5MHz ) -
Conductor DC Resistance22AWG ≤ 60Ω/km
24AWG ≤ 94.2Ω/km
18AWG ≤ 23 Ω/km
15AWG ≤ 60Ω/km
|
Product |
Product |
Ground |
Out |
Nominal Outside |
Copper Weight |
Cable Weight |
|
W0784604714142727VT |
1X2X15AWG/19 // 1X2X18AWG/19 |
18AWG |
PVC |
11.0 |
75 |
163 |
|
W0784604713142727VT |
1X2X22AWG/19 // 1X2X24AWG/19 |
22AWG |
PVC |
6.8 |
24 |
60 |
Return to List 